Product detail:
Specification avr 265-06 avr 265-06s Power output 6 amp dc at 65 vdc max. Continuous. Minimum field resistance 11 ohm. Input power requirement single or 2-phase 50 to 400hz,180 to 240 vac. External voltage adjust rheostat 10k ohm 2w potentiometer. Regulation accuracy + 0.5% of voltage set point, average responding Voltage drift + 0.5 % voltage variation for a 40o c (104o f) changes in ambient temperature. Response time < 4 miliseconds. Frequency compensation provision for automatic voltage build-up from generator residual voltage as low as 24 vac Emi suppression internal filter Voltage built-up 24 volt ac Over-excitation shutdown over-excitation shutdown protection reduces the output voltage to zero for the following voltage in the time shown. 125 vdc 10% in approximately 10 seconds,210 vdc 10% in approximately 1 sec or less. Droop/line drop compensation <10 va adjustable from 0 - 10% of rated input current,0.8 power factor. (ldc compensates for voltage drop due to line reactance and reactive components of the load current only) Operating & storage temp - 40 c to + 70 c (-40 f to + 158 f) Relative humidity 95% non-condensing Shock withstand 20g in each of the three mutually perpendicular planes. Vibration withstand the following accellerations at the stated frequency:4.5g; 18 to 2000hz Weight + 300 grams + 500 grams