VII.D : 96kV Surge arrester
Standard IEC 99-4
Surge arrester with lightning register: Zinc Oxide type
Service condition Outdoor.
System voltage 110kV
Max. Continuous operating voltage Uc > 77 kV
Temp. overvoltage capability for 1s TOV > 108.3 kV
Rated voltage: Ur = 96 kV
Rated frequency 50Hz
Method of neutral grounding Directly grounded
Nominal discharge current 10,000A
Maximum residual voltage at indicated impulse current of 8/20s 256kV
Creepage distance of housing 25 mm/kV
Insulation level of arrester housing:
- Rated power frequency withstand voltage 230 kV
- Rated lightning impulse withstand voltage 550 kV
Line discharge class 3
Minimum energy absortion capability 4.5 kJ/kV Ur
Accessories:
+ Zinc galvanized Supporting structure, bidder must provide shop drawing for manufacturing the steel structure.
+ Terminal for conductor 185 mm2, earthing terminal
+ Document for installation, operation, maintenance, and test report.
VII.E: 72kV Surge arrester:
Standard: IEC-94-4
Technical parameters:
Type: outdoor, metal - oxide surge arrester without gaps.
Service system voltage: 115kV.
Rated voltage: 72 kV.
Max. Continuous operating voltage: 57 kV (rms)
Nominal discharge currents (8/20s): 10kA.
Residual voltage (Impulse 8/20s - Discharge current 10-kA crest): 192 kV.
Line discharge class: 3
Minimum energy absorption capacity: 4.5kj/kV Ur
Accessories:
Zinc galvanized Supporting structure, bidder shall provide shop drawing for manufacturing the steel structure.
Surge Counter
Terminal connectors for conductor ACSR-185 and earthing terminals
Insulator base.
Document for installation, operation, maintenance, and test report.
Special note: Bidder provide following document for bid evaluation.
- Type test certificate (as per IEC99-4).